Since the current in each phase in a three-phase system is balanced, and with a phase difference of 120 degrees, the sum total current approaches zero, the neutral line is not needed for three-phase motors. A motor with the proper connections to a three-phase power source will run with no neutral line.
Table of Contents
TogglePower Basics
To understand why three-phase motors do not require a neutral line, first, some basics need to be understood about the power systems. Power systems are usually classified into single-phase and three-phase. Single-phase is traditionally used in homes and small commercial applications, while three-phase power is supplied in industrial and large commercial applications. The reason is that three-phase power supplies have higher transmission efficiency and larger power output, which is beneficial for high-power equipment and long-distance transmission.
The basic concept in three-phase power is that each of the phases – or “lines“ – carries a current that possesses a 120-degree phase shift from the others; thus, over time, each line’s current oscillates. This phase shift in the design enables three-phase power to naturally balance currents in transmission whereby each phase current compensates the others to reduce losses. This balance enables the three-phase system to handle more power efficiently without loss of system stability. In contrast, single-phase systems are inefficient since, within one cycle, they can only provide current along one path, thereby easily causing voltage fluctuations.
With a three-phase system, the current in one phase can effectively cancel out the other phases due to the phase angle differences. Because of this mutual cancellation, the reactive power within the system will be much reduced, resulting in reduced losses and improving the efficiency of transmission. For this reason, three-phase systems find widespread use in motors and industrial equipment, while single-phase power is mainly applied to low-power and household applications.
What’s Neutral
In power systems, the neutral line gives a path for return current and stabilizes the voltage. The flow of current is from the hot line, or phase line, through the load back to the power source through the neutral line, forming a closed circuit in single-phase power systems. This line voltage is usually neutral, with the same value as the ground potential, because it acts for protection against overvoltage. The neutral line may balance voltage fluctuations, especially when the voltage is not quite stable, and, therefore in general, it acts as a balancing factor in the circuit.
The function of a neutral line is different in three-phase systems. Each current of phases is out of phase by 120 degrees in three-phase systems. If the load on such a three-phase system is balanced, then each phase’s current will offset each other within that system. This brings the total current in the system close to zero; hence, in theory, an extra line to return the current is not required. In other words, the three-phase system does not require a neutral line to complete the circuit.
In some three-phase four-wire systems, there may be a neutral line present; usually, this would be the case where it acts as some sort of “backup” in case of load imbalance, rather than one which is needed for operation of the motor. Since the operation of three-phase motors is based on such a principle, they can inherently balance the load and hence do not require any support from neutral lines.
3-Phase Magic
Indeed, three-phase systems are often referred to as the “magic of electrical engineering”. That is not without a reason: three-phase systems make full use of the phase difference in forming a “balanced triangle” of voltage and current between the three phases, which gives very advantageous properties concerning motor operations. It is a three-phase current wherein, in each cycle of the alternating current, phase angles remain 120 degrees apart; thus, at every instant, one of the phases is at peak voltage, while the other two are smaller. Such a design creates a more stable and uniform power output.
The three-phase motors are unique because of the utilization of a rotating magnetic field given by a three-phase power. The result is a rotating magnetic field because of the phase angle differences among the three phases. As long as this kind of rotating field exists, the motor rotor is able to rotate naturally without a starting capacitor, which makes the motor design much simpler and reduces inefficiency in operation. The characteristics of this rotating magnetic field provide an assurance of smaller mechanical loss, faster start-up, and higher torque at lower currents. This makes the three-phase motors industrially used and at high power because of their efficiency and reliability.
Because the torque and current are distributed uniformly among the various phases, the different phases prevent the problem of load imbalance that usually characterizes single-phase motors. The rotor will be smoothly and continuously rotated inside the magnetic field, which reduces vibration and noise in a three-phase motor. Such smoothness allows the three-phase motors to work stably for long periods and adapts to the demands of complex industries.
Balanced Loads
The explanation of why there is no need for a neutral line lies in the very concept of balanced loads in a three-phase power system. In an ideal three-phase system, the currents in the three phases have a 120-degree phase difference, and with this, the system reaches self-balance in case the load is perfectly symmetrical, that is, the vector sum of the three-phase currents is zero; thus, the total current at each moment is almost zero in this system. This eliminates the requirement for a neutral line to complete the existing loop.
For practical purposes, a three-phase motor is said to be an almost balanced load since three-phase motors are designed to provide symmetry in each phase load as much as possible. Three-phase motors are connected either in star or delta configurations. Generally, star connections are used in high-voltage systems, whereby the voltage of each phase is divided, whereas low-voltage systems normally make use of delta connections that, although can provide higher starting torque. Whatever the connection may be, in a three-phase motor, the load balance is maintained, and hence the phase loads are approximately the same throughout the system.
It is quite hard for complete load balance in practice, owing to some equipment that might cause slight differences in the phase currents. If this happens, a three-phase four-wire system – meaning a three-phase system with a neutral line – can provide a current loop to balance the load in the system. However, most of the time, the design of three-phase motors is good enough with no need for an extra neutral line.
No Neutral Needed
There is, in fact, a very simple reason why neutral line is not needed to begin with. It directly relates to the design of three-phase systems where it allows the currents to form a closed loop within the system – meaning, no need for an additional neutral line. In any instant of time in a three-phase system, the sum of the current in each phase is approximately zero, hence keeping natural current balance. The system can provide cancellation of current across the three hot wires, thereby not needing a neutral line for return flow.
A working three-phase motor already has a fairly large resistance; adding a neutral line can only further introduce more resistance, adding to the losses and complicating the circuit. This is especially the case when motors have to be driven over long distances. The presence of a neutral line adds length and cost to cables. It thus makes complete logical and economic sense to also avoid the use of a neutral line in the design of a three-phase motor because it minimizes energy losses during the transmission of power.
For some industrial applications, the configuration may also include a neutral line so as to support loads that are unbalanced – such as lighting or other small single-phase devices. In these cases, the neutral provides some sort of “buffer” in the system rather than being an integral part of motor operations. Because the neutral lines are seldom used in the industry for three-phase motors, the three-phase suffices for stability and efficiency of operation.
Efficiency Boost
By getting rid of one neutral line within three-phase motors, there is not only simplification within the system but also great improvement in the performance of the overall system. Sometimes the neutral line can add a lot of resistance to a system and, hence, is capable of creating greater power losses within it. By not having the neutral line, current will flow only between the three phases, further reducing energy loss. Furthermore, since they efficiently convert more electrical energy to mechanical, the full capacity of the balanced power output of the three-phase system can be utilized by the three-phase motors.
Besides, it would also save money for industrial users because it requires less wiring when no neutral line is used. In particular, the cabling cost for long-distance transmission may be increased by one neutral line. Where three-phase motors do not require a neutral line, initial expenses are lower, line losses reduced, and maintenance costs cut in the future.
This characteristic feature of a three-phase motor makes their operational efficiency higher because the rotating magnetic field created at the stator allows smooth starting and operation of the motor without any additional starting devices, hence reducing energy losses. In the case of a three-phase motor, the current is evenly distributed; this eliminates load imbalance found in single-phase motors and results in an increased operating life.
Common Myths
There are a lot of general misconceptions regarding three-phase motors and their relation with the neutral line. Typical misconceptions are that without the neutral line, the three-phase motors will wobble or not function. In reality, three-phase motors do not require a neutral line because the three-phase system balances itself, forms a stable loop, and works fine without it. It means a three-phase motor will work with just three hot wires, creating a closed circuit in the system.
Another myth is that the absence of a neutral line reduces the safety of a three-phase system. Actually, it is so designed to ensure safety for three-phase motors. There are also protection means against current leakage or voltage fluctuations through grounding systems in the motor itself and power lines. Moreover, in three-phase motors, the load design is usually balanced; therefore, an absent neutral line does not create much deviation in current.
Some even argue that three-phase motors need an absolute balance of the load for their normal working. Although a balanced load is considered ideal, yet the design of the three-phase systems can tolerate the imbalance to a certain degree. The majority of the industrial designs of three-phase motors are by default sufficiently close to a balanced arrangement that they will not have any negative impact on the system.